MELSOFT Library

FB library for the L60AD4 (CC-Link IE Field compatible) (other languages)

This FB library is for the MELSEC-L series analog-digital converter module (CC-Link IE Field compatible).

Applicable model L60AD4
File name Size Last update Version
fb-l60ad4-ief_v110l_e.zip 5,675,984 bytes Jun. 16, 2016 1.10L
Relevant manual Type Language
FBM-M071-A MELSEC-L Analog-Digital Converter Module FB Library (CC-Link IE Field compatible) Reference Manual English
FBM-M169-A Chinese (simplified)
FB name Function name Description Ver.
M+L60AD4-IEF_ReadADVal Read A/D conversion data Reads the A/D conversion data of a specified channel. 1.00A
M+L60AD4-IEF_ReadAllADVal Read all A/D conversion data Reads the A/D conversion data of all channels. 1.00A
M+L60AD4-IEF_ReadScalingVal Read scaling value Reads the scaling value (digital operation value) of a specified channel. 1.00A
M+L60AD4-IEF_ReadAllScalingVal Read all scaling values Reads the scaling values (digital operation values) of all channels. 1.00A
M+L60AD4-IEF_SetConvertSpeed Conversion speed setting Sets the conversion speed. 1.00A
M+L60AD4-IEF_SetADConversion Enable/disable A/D conversion Enables or disables A/D conversion for a specified channel or all channels. 1.00A
M+L60AD4-IEF_SetAverage Averaging process setting Configures averaging processing settings of a specified channel. 1.00A
M+L60AD4-IEF_SetScaling Scaling setting Configures scaling settings of a specified channel. 1.00A
M+L60AD4-IEF_SetProcessAlarm Process alarm setting Configures process alarm settings of a specified channel. 1.00A
M+L60AD4-IEF_SetInputSignalErr Input signal error detection setting Configures input signal error detection settings of a specified channel. 1.00A
M+L60AD4-IEF_RequestSetting Operating condition setting request operation Makes changes made to each function's operational condition settings effective (valid). 1.00A
M+L60AD4-IEF_SetOffsetVal Offset setting Sets the offset value of a specified channel. 1.00A
M+L60AD4-IEF_SetGainVal Gain setting Sets the gain value of a specified channel. 1.00A
M+L60AD4-IEF_ShiftOperation Shift operation Adds the shift amount to the digital value that was input. 1.00A
M+L60AD4-IEF_DiffOperation Differential conversion process Outputs the difference obtained by subtracting the standard value from the digital value that was input. 1.00A
M+L60AD4-IEF_ErrorOperation Error operation Monitors error codes and resets errors. 1.00A
M+L60AD4-IEF_OGBackup Offset/gain value save Reads the offset/gain setting values in the user range setting and saves them to a file. 1.00A
M+L60AD4-IEF_OGRestore Offset/gain value restore Restores the offset/gain setting values saved in the file to the module. 1.00A
M+L60AD4-IEF_SetInputSignalErrExp Input signal error detection extension setting Sets the input signal error detection extension setting of a specified channel. 1.00A
M+L60AD4-IEF_SetDigitalClip Digital clipping setting Enables or disables the digital clipping of a specified channel. 1.00A
M+L60AD4-IEF_SetShift Shift setting Configures the shift setting of a specified channel. 1.00A
M+L60AD4-IEF_SetLoggingPARAM Logging function parameter setting Configures the logging function settings of a specified channel. 1.00A
M+L60AD4-IEF_SetFlowRatePARAM Flow amount integration function parameter setting Sets the flow amount integration function of a specified channel. 1.00A
M+L60AD4-IEF_SaveLogging Logging data save Saves the logging data of a specified channel in a file. 1.00A
M+L60AD4-IEF_MakeFlowRateReport Flow amount daily report creation Saves the flow amount daily report data of all channels in a file. 1.00A


[Precautions for using the file]

Install the FB library to the personal computer in which GX Works2 of the following version has been installed.

  1. GX Works2(Japanese): Version 1.86Q or later
  2. GX Works2(English): Version 1.24A or later
  3. GX Works2(Chinese (simplified)): Version 1.49B or later
  4. GX Works2(Chinese (traditional)): Version 1.49B or later
  5. GX Works2(Korea): Version 1.49B or later


[How to extract the compressed file]

Copy the file to a folder.
After the copied file is decompressed, the fb-l60ad4-ief_v110l_e folder is created.

Decompression method 1): For the OS with the ZIP-compatible decompression function

  1. Right-click the copied file.
  2. Select "Extract All...".
    When "Extract All..." is not displayed, follow the decompression method 2).
  3. Specify the location of the extracted file, and click the "Extract" button to start the decompression.

Decompression method 2): For the OS without the ZIP-compatible decompression function

  1. If not having the ZIP-compatible decompression tool, acquire the decompressing tool.
  2. Decompress the file using the decompression tool.

* Use the decompression tool at users' own risk.


[Installation method]

  1. Execute setup.exe in the fb-l60ad4-ief_v110l_e folder.
  2. Install the FB library following the messages of the installer.


[How to use MELSOFT Library]

  1. Select [Library] - [Install...] from the [Project] menu.
  2. In the [Import Library to Project] dialog box, select the installed library and necessary FBs, and click the [OK] button.
  3. Paste the FB from the [Element Selection] window to the program.


[Precautions for using MELSOFT Library]

  1. Before applying the FB library of MELSOFT Library to a system, check sufficiently if no problem occurs in the control of the system.